Monday, July 20, 2009

Finishing the refrigerator conversion project

In my last post, I had just finished charging the "new" refrigerator with R134a. I was surprised that it worked at all, and it was still working the next day, so something must be correct. I used some expanding foam to fill up the large square hole left by the thermoelectric module in the bottom of the fridge. The clear vinyl tube is a hose that I connected to a drain on the inside of the fridge. If (when) the evaporator defrosts, I am sure there will be a fair bit of condensate dripped out. I put a small stainless tray on top of the compressor to catch the water.

I also used the fridge's existing thermostat (the white tube on the right). The manufacturer setup the thermostat so that it would regulate the temperature on the evaporator itself. The thermostat has a capillary tube that is clipped onto the evaporator and a large knob with numbers 1 to 7 (like any refrigerator). I also filled up the hole through which the refrigerant lines and thermostat enter the fridge with expanding foam.



While the existing thermostat works well, the table has a nice cutout for a two-digit 7-segment display and four buttons. The thermoelectric fridge came with a digital thermostat, and I made the cutout in the tabletop specifically for it. I would like to keep the digital thermostat feature, so I am building one with an Arduino microprocessor.

Here is the rear of the completed table with white thermostat control knob at lower left. I've already written some Arduino code for the digital thermostat, and will probably be implementing that soon. In the meantime, my table refrigerator is now frosty cold, and using less power than the thermoelectric model.

Friday, July 17, 2009

Retrofitting a thermoelectric refrigerator with a conventional compressor system

A couple years ago, I built a nice wooden table that housed a small refrigerator. The idea is that it keeps drinks handy in the living room for parties and guests. It's also cool, and fits with my idea of what "functional furniture" should be.

I chose a refrigerator meant for storing wine because it had a nice glass door, was pretty small, was very quiet, and could operate facing upwards because the thermoelectric device doesn't care about its orientation. I knew that thermoelectric refrigerators generally suck at actually refrigerating, and this one was not exception.
On really hot days, the fridge would get up to 5o-60*F, which is cool, but not nearly as nice as drinking 40*F beverages. The other problem is that it draws 70W, essentially constantly. This comes out to 613 KWh/year. Most small conventional refrigerators use around 300 KWh/year. Also, I like to tinker and wanted to mess around with a refrigerant system.



I bought a small 1.8 cu ft Haier fridge off craigslist for $15. Geez, can't beat that! My first task was to pull out all of the system components from the insulated box. This required draining the system of refrigerant through a small hole that I drilled in the compressor fill tube. Before doing this, I checked the label, and it indicated the system used 1.6oz of R134a. I can buy R134a at the auto parts store, so I will be able to refill the system.


I de-soldered the tiny capillary line from the accumulator / dryer and de-soldered the suction line on the compressor. I used an oxy-acetylene torch to heat the joint, then I just pulled the tubes apart when the solder became molten.

Here is the evaporator liberated from the fridge.



Luckily, with one flap unfolded, the evaporator fit perfectly in the thermoelectric cooler (TEC) fridge.


I mounted the compressor underneath the table (also getting very lucky that there was enough clearance). I cleaned the copper tubes carefully, then re-soldered them with silver solder and some paste flux. I had to extend the suction tube by a few inches, and so I just got some tube that fit around the existing line and soldered it to the outside.


I soldered the capillary tube back into the dryer, and put a valve on the compressor fill tube. The system was sealed at this point. Now, I connected my vacuum pump (Welch 1400) with a micron vacuum gauge and a tee that connected to a can of R134a. I positioned the can on a sensitive scale so that I could meter out 1.6 oz of refrigerant.

I pulled a 375 micron vacuum in about 15 minutes or so. I even ran the compressor while the system was under vacuum. It raised the pressure just a couple hundred microns, then it settled back down quickly, so I felt the system was dry and sealed.


After I metered out 1.6oz, which only took a few seconds with the valve just cracked open, I tightly closed the valve that I added to the fill tube, and was very pleased to see feel the evaporator getting very cold.

Tomorrow, I will re-insulate the TEC fridge and hopefully give it a final test.